توضیحات

Voltage Repeater KFD2-VR4-Ex1.26

pepperl-fuchs

1-channel isolated barrier
24 V DC supply (Power Rail)
Voltage input 0 V … -20 V
Vibration sensor inputs
Voltage/current field supply
Voltage output 0 V … -20 V
Up to SIL 2 acc. to IEC 61508

Voltage Repeater KFD2-VR4-Ex1.26

pepperl-fuchs

General specifications
Signal type Analog input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Supply
Connection Power Rail or terminals 11+, 12-
Rated voltage 19 … 30 V DC
Ripple within the supply tolerance
Power dissipation ≤ 1.2 W
Power consumption ≤ 1.6 W
Input
Connection side field side
Connection terminals 4 (common), 1, 3 and 5 (supply -), 2 and 6 (signal -)
Input resistance 10 kΩ terminals 4 (common), 6-/2-
Output rated operating current terminals 4 (common), 5-: > 10 mA at -21 V or > 20 mA at -18 V
terminals 4 (common), 1-: 5.3 mA ±0.4 mA at -10 V
terminals 4 (common), 3-: 3.6 mA ±0.7 mA at -10 V, 20 °C (68 °F)
Transmission range -20 … 0 V
Output
Connection side control side
Connection terminals 7-, 8+
Voltage -20 … 0 V
Load ≥ 9 kΩ (3-wire sensor), ≥ 2 kΩ (2-wire sensor)
Output resistance 24 Ω typ., 27 Ω maximum
Since this is much less than the end-to-end resistance of a zener barrier, it may be necessary to specify a monitor intended for use without a barrier. Please follow the advice of the monitor manufacturer.
Transfer characteristics
Cut-off frequency 10 kHz (-0,1 dB)
20 kHz (-1 dB)
Deviation DC transfer error (with 10 kΩ load) < 10mV
After calibration additional error with AC superimposed is ±5 mV at 20 °C (68 °F) at any point within the span, provided that the alternating component of the input voltage is not excessive, e. g.
– square waves (0 … 20 kHz): 5 Vpp
– sine waves (0 … 20 kHz): the full span of 20 Vpp (= 100 g peak acceleration at 100 mV/g) is acceptable.
Influence of ambient temperature (< 100 ppm of span)/K at any point within the span
Time delay relative to input 7.1 ±0.3 µs
Ripple in 200 kHz bandwidth < 20 mVrms
in 20 kHz bandwidth < 3 mVrms
Galvanic isolation
Output/power supply functional insulation, rated insulation voltage 50 V AC
Indicators/settings
Display elements LED
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibility NE 21:2017
EN IEC 61326-3-2:2018
Degree of protection IEC 60529
Protection against electrical shock UL 61010-1
Ambient conditions
Ambient temperature -20 … 60 °C (-4 … 140 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass approx. 125 g
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificate BAS 02 ATEX 7206
Marking Ex-Hexagon II (1)GD, [Ex ia Ga] IIC, [Ex ia Da] IIIC, (-20 °C ≤ Tamb ≤ 60 °C) [circuit(s) in zone 0/1/2]
Input Ex ia Ga, Ex ia Da
Voltage -26.4 V
Current 90 mA
Power 570 mW
Supply
Maximum safe voltage 253 V (Attention! The rated voltage can be lower.)
Output
Maximum safe voltage 253 V (Attention! The rated voltage is lower.)
EU-type examination certificate DMT 01 ATEX E 133
Marking Ex-Hexagon I (M1) [Ex ia] I
Certificate TÜV 99 ATEX 1499 X
Marking Ex-Hexagon II 3G Ex nA II T4 [device in zone 2]
Galvanic isolation
Input/Output safe galvanic isolation acc. to IEC 60079-11, voltage peak value 375 V
Input/power supply safe galvanic isolation acc. to IEC 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000
International approvals
UL approval
Control drawing 116-0316 (cULus)
IECEx approval
IECEx certificate IECEx BAS 05.0078
IECEx BAS 10.0085X
IECEx marking [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Ex nA II T4 Gc
General information
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Accessories
Optional accessories – power feed module KFD2-EB2(.R4A.B)(.SP)
– universal power rail UPR-03(-M)(-S)
– profile rail K-DUCT-BU(-UPR-03)

Voltage Repeater KFD2-VR4-Ex1.26

pepperl-fuchs

If you need a specific Voltage Repeater KFD2-VR4-Ex1.26 firmware or series, then we probably have it. Please call or email us your request.

call: +982188856017
Email: info@hermestrading.ir

شركت هرمس نیلگون مایا با هدف ارتقاء سطح كيفي تجهيزات فني و آزمايشگاهی، نفت، گاز، پتروشیمی، دانشگاهی، عمرانی و همچنين تامین تجهیزات  روز دنيا به كشور ايران وارد اين عرصه گرديده.
اين شركت با اعتماد قابل تقدير شما عزيزان توانسته است در مدت زماني كوتاه با كسب موفقيت های چشمگير، نامی قابل اعتماد در زمينه تامین تجهيزات نوين و پيشرفته فنی و آزمايشگاهی در سراسر كشور داشته باشد.
ما با حضوری فعال و کم نظیر سعی نموده ایم تا با مشاوره فنی، معادل و بهینه سازی تجهیزات مورد نیاز، انبار موجودی و امکان تحویل فوری، دفاتر برون مرزی در اروپا و آسیا و عاملیت فروش برند های معتبر و فعال در صنعت کشور، موجبات تامین آسوده، کم هزینه و ایمن را برای کاربران خود فراهم آوریم و گامي مهم در زمينه تامین کالا  و ارائه تجهيزات پيشرفته در صنعت نفت، گاز، پتروشیمی برداریم. با ما در تماس باشید.

Voltage Repeater KFD2-VR4-Ex1.26

pepperl-fuchs

1 دیدگاه برای KFD2-VR4-Ex1.26

  1. شرکت هرمس نیلگون مایا

    با ما در تماس باشید صفحه تماس با ما ——> اینجا کلیک کنید

دیدگاه خود را بنویسید

نشانی ایمیل شما منتشر نخواهد شد. بخش‌های موردنیاز علامت‌گذاری شده‌اند *